INFLUENCE OF PLL ON BROADBAND OSCILLATION UNDER WEAK GRID

Y. Ren,H. Liu,L. Wu,Y. Li,Y. Min
DOI: https://doi.org/10.1049/icp.2021.2221
2021-01-01
Abstract:The integration of large-scale renewable energy into the weak power grid has aroused a series of broadband oscillation problems. Converter is an important link between renewable energy and power grid, in which phase locked loop (PLL) can track the phase angle and frequency of power grid. At present, the influence of PLL parameters on system stability is often studied. With the increase of PLL bandwidth, the frequency range of converter negative damping increases, and the system is prone to broadband oscillation. This paper further studies the influence of the coupling between PLL and the steady-state operation point. The converter admittance can be divided into two parts. One part is only related to the converter circuit and control, and the other affected by the interaction of PLL and the operation point. Then, the system stability is analysed according to the generalized Nyquist criterion (GNC), and the grid impedances and converter power levels required for the system stability are given. The research can provide reference for field test and operation.
What problem does this paper attempt to address?