Optimization Strategy and Stability Analysis of Grid-Connected Inverter Based on PLL Positive Sequence Grid Voltage Feedforward in Weak Grid

Zhipeng Peng,Bin Wang,Wanwan Xu,Yong Yan
DOI: https://doi.org/10.1109/cac53003.2021.9728116
2021-01-01
Abstract:This paper mainly studies the stability of three-phase LC grid-connected inverter system under weak grid. The current research considers that the negative effect of voltage feedforward link, high bandwidth of phase-locked loop and improper design of current loop control parameters will have adverse effects on the system stability. In view of the above adverse factors, the paper analyzes the change rule of the influence of the above factors on the system stability through frequency domain analysis method. The control parameter optimization strategy of grid-connected inverter based on PLL positive sequence grid voltage feedforward is proposed. It is found that the system stability can be enhanced by increasing the value of proportional coefficient in the current loop proportional integral control and using the phase-locked loop positive sequence voltage feedforward strategy. In addition, increasing the ratio of proportional and integral coefficients can reduce the bandwidth of the PLL and enhance the stability of the system, and a definite range of ratio is given. Finally, a simulation platform is used to verify the correctness of the theoretical analysis and the effectiveness of the proposed scheme.
What problem does this paper attempt to address?