Abstract:The overcurrent fault of copper wire is an important cause of electrical fire, and the combustion process of which is relatively complicated. In this study, the rated current of 32A of the wire was taken, and the electrical fault simulation device was used. After the overcurrent Io was set to 128A, 160A, 192A, and 224A, respectively, to analyze the combustion evolution process of PVC‐insulated copper wire, the evolution of pyrolysis gas from the insulating layer, and the change of functional groups. The results show that when the overcurrent fault of PVC‐insulated copper wire happened, the core wire was turning red, the wire was deforming, the smoke was releasing, the insulating layer was dripping, the wire was fusing, and the continuous burning occurred. When the current Io