Theoretical and Experimental Research on the Performance of Twin Screw Compressor Using R513A As R134a Replacement

Zhiping Zhang,Ying Wang,Xiaokun Wu,Xi Pan,Ziwen Xing
DOI: https://doi.org/10.1177/0954408920951141
2020-01-01
Abstract:The refrigerant R513A receives significant attention as an alternative to R134a used in water chiller, due to its lower global warming potential. However, whether R513A can directly and efficiently take the place of R134a in the twin screw compressor has not been verified. In this paper, a thermodynamic model is applied to compare the performance of R513A and R134a in a twin screw compressor. The leakage process and heat transfer between refrigerant and lubricant oil are taken into account. With this model, the volumetric efficiency and adiabatic efficiency are simulated and p- V indicator diagram is presented. Simulated results show that R513A is the refrigerant with low temperature lift, low pressure ratio but high pressure difference. Experimentally, the test compressor originally designed for R134a is used to compare the performance of R134a and R513A. Test results show that the differences of volumetric efficiency and adiabatic efficiency between R134a and R513A are very small and acceptable. The COP of R513A is only a little bit lower than that of R134a. Hence, taking the cost of replacing equipment and GWP into account, R513A can directly take the place of R134a in the twin screw compressor.
What problem does this paper attempt to address?