Effect of Voltage on Thomson-Coil Actuator for Fast Mechanical Switch

Yannan Zhou,Yulong Huang,Weijie Wen,Chao Yang,Bin Liu,Maoliang Hu,Yu Bai
DOI: https://doi.org/10.1007/978-3-030-31680-8_129
2020-01-01
Abstract:The fast mechanical switch equipped with the Thomson-coil actuator is one of the key devices in hybrid HVDC circuit breaker. And electromagnetic damping technology can solve the problems of high-speed damping operation without adding additional mechanical parts. In order to make the opening/closing operation process as unified as possible, the driving and damping voltages are the same in the previous research. In this paper, the effects of different combinations of driving and damping voltages on the travel characteristics have been studied. Voltage combinations are divided into three types. The first type is to change the driving and damping voltage at the same time; the second is to keep the damping voltage constant and change the driving voltage; the last type is to keep the driving voltage constant and change the damping voltage. In order to ensure that the contacts system can move to the isolating distance in 3 ms, the driving voltage should not be reduced. At the same time, in order to ensure a better damping effect, the buffer start time range should be as large as possible. Therefore, it is suggested that the damping voltage is 2%–4% lower than the driving voltage. A fast simulation method based on equivalent circuit method, which avoids lots of test operations, has been proposed in this paper. It can provide reliable references for the application and improve the feasibility and reliability of fast mechanical switch in engineering.
What problem does this paper attempt to address?