Backup Protection for Tie Lines in a Double-Petal-mode Distribution Network

Jingkai Kong,Yuejia Li,Wujiapin Yao,Yi Zhao,Jiaxing Zhou,Tao Zheng
DOI: https://doi.org/10.1109/iceemt52412.2021.9602456
2021-01-01
Abstract:The double-petal-mode distribution network is much reliable power supply. However, its topology is complex and many tie lines are used. A backup protection scheme of tie lines is proposed in this paper. The principle of multi-terminal differential protection and the direction of power flow are used to determine the fault location on the tie lines. The network model is established by PSCAD / EMTDC to verify the effectiveness of the protection scheme. The result shows that, compared with other backup protections, this protection can greatly shorten the time to isolate the fault. It can also reduce the number of measurement equipment in the system.