An Analytical Two-Machine Equivalent Method of DFIG-Based Wind Power Plants Considering Complete FRT Processes

Pupu Chao,Weixing Li,Xiaodong Liang,Shiyun Xu,Yong Shuai
DOI: https://doi.org/10.1109/tpwrs.2021.3054871
IF: 7.326
2021-01-01
IEEE Transactions on Power Systems
Abstract:In this paper, an analytical two-machine equivalent method of DFIG-based wind power plants (WPPs) is proposed. Through simulations of a 49.5 MW WPP, the root causes of errors of the single-machine equivalent are identified. Taking a four-machine WPP as an example, analytical expressions of fault-ride through (FRT) behaviors of the WPP model and its single-machine equivalent model are derived, and root causes of errors are revealed in theory including: inconsistent transient power behaviors in the initial FRT stage; unequal quasi-steady-state active power during a fault; and mismatching initial points and ramp rates of active power after the fault clearance. To eliminate equivalent errors, an improved equivalent method is proposed with two steps: 1) Group wind turbines into two clusters by the crowbar actions and represent them as two equivalent machines; 2) Correct their controller reference settings based on the derived FRT behavior expressions of the detailed WPP. Simulation results verify that the proposed method can accurately reproduce FRT behaviors of the WPP under various wind scenarios and voltage dips.
What problem does this paper attempt to address?