Exergy analysis of 1 000 W double reheat ultra-supercritical power plant

苏胜,司宁宁,赵志刚,向军
DOI: https://doi.org/10.13245/j.hust.170317
2017-01-01
Abstract:The performance of a 1 000 MW double reheat ultra-supercritical (USC) power plant was evaluated.An exergy analysis was performed to direct the energy loss distribution of this steam cycle and the unit model was established by the software ASPEN PLUS.The exergy balance equation,the exergy loss and the exergy efficiency were established and calculated.The main points of exergy loss in the power plant were determined,in order to provide insights of work capacity and energy-saving optimization of the double reheat USC unit.The results show that the biggest exergy loss occurred in furnace is caused by combustion of fuel and followed by heat exchange of water wall.The exergy loss of turbine mainly focuses on the very high pressure turbine and the low pressure turbine.The exergy efficiency in this type unit is 2.8% higher than that in traditional units.The low pressure turbine allow lower exhaust steam parameter,lead to the exergy loss in condenser is reduced by half than in single reheat unit,and the utilization is more reasonable.