Performance Analysis of Gas Engine Heat Pump Retrofitted with Energy Storage Unit in Heating Season

Zhao Yang,Yide Gao,Qiang Zhang,Ning Li
DOI: https://doi.org/10.11784/tdxbz201707002
2018-01-01
Abstract:According to the hourly changing characteristics of building heat load in atypical winter day and operating performance of gas engine heat pump,an energy storage unit was added to gas engine heat pump system.The heat balance model and evaluating indicator were established.The energy storage/release strategy and the partition of system operating mode (Mode L,P,F and O) were designed based on the wave range of building heating load.A test of the system has been designed.The experimental result shows that the gas engine could entirely work in the economic speed zone (1 200-2 000 r/min) after adding the energy storage unit.The daily average primary energy rate in heating season (PERh) is 1.48 which is 4.2% higher than that of the traditional gas engine heat pump.The quantity of fuel consumption is reduced by 12.5%.At the same time,the energy storage unit could balance the relationship between the heating capacity of gas engine heat pump system and the demand of real-time building heating load well.