Exploring Heating Performance of Gas Engine Heat Pump with Heat Recovery

Fu-jiang Dong,Feng-guo Liu,Xian-ting Li,Xue-yi You,Dong-fang Zhao
DOI: https://doi.org/10.1007/s11771-016-3249-z
2016-01-01
Journal of Central South University
Abstract:In order to evaluate the heating performance of gas engine heat pump (GEHP) for air-conditioning and hot water supply, a test facility was developed and experiments were performed over a wide range of engine speed (1400-2600 r/min), ambient air temperature (2.4-17.8 °C) and condenser water inlet temperature (30-50 °C). The results show that as engine speed increases from 1400 r/min to 2600 r/min, the total heating capacity and energy consumption increase by about 30% and 89%, respectively; while the heat pump coefficient of performance (COP) and system primary energy ratio (PER) decrease by 44% and 31%, respectively. With the increase of ambient air temperature from 2.4 °C to 17.8 °C, the heat pump COP and system PER increase by 32% and 19%, respectively. Moreover, the heat pump COP and system PER decrease by 27% and 15%, respectively, when the condenser water inlet temperature changes from 30 °C to 50 °C. So, it is obvious that the effect of engine speed on the performance is more significant than the effects of ambient air temperature and condenser water inlet temperature.
What problem does this paper attempt to address?