Stray current corrosion behavior of Q2 3 5 carbon steel grounding material

Liwei ZHU,Bingkun YANG,Min LIU,Jiaxiu HU,Zhouhai QIAN
DOI: https://doi.org/10.3969/j.issn.1000-1565.2016.05.008
2016-01-01
Abstract:On the base of stray current corrosion (SCC ) problems in the grounding grid service process,the corrosion behavior of Q235 carbon steel grounding material under simulation of AC or DC stray current interference conditions was studied by means of potential,current and corrosion weight loss measurement,and the corrosion morphology and products were characterized by SEM and XRD.The results showed that SCC had concentrated corrosion characteristics and the AC or DC SCC product layer was por-ous and had obvious crack,delamination and detachment,which implies its uselessness to protect the ma-trix.The corrosion products mainly consisted of Fe3 O4 and Fe2 O3 .The results of weight loss measurement showed that the corrosion rate of Q235 steel was increased under AC or DC stay current interference condi-tions and the corrosion rate of DC SCC was about 1 8 times of AC SCC under the same current density.SCC had obvious electrolytic corrosion characteristics.The area where current flowing into was protected as the cathode and the current outflow area was corroded as the anode.
What problem does this paper attempt to address?