Spatiotemporal Change Rules of Water Quality in Cut-off Water Pipelines in District Metering Areas (DMA)

CHEN Da,LIU Jing-qing,CHEN Huan-yu,WANG Ruo-wei
DOI: https://doi.org/10.3785/j.issn.1008-973x.2019.09.009
2019-01-01
Abstract:The pilot platform was constructed with water pipelines of nine years old to study the spatiotemporal changes of essential physical, chemical and biological parameters of water in cut-off pipelines, in order to explore the potential impact of cut-off pipelines and stagnant areas which are created in the construction of district metering areas (DMAs) on water quality. Results show that, as the depth of cut-off pipeline increases, the biofilm and limescale fall off more quickly and the water quality deterioration rate gets faster; the temporal changes of iron release, turbidity and microorganism vary with time at different depths. After twelve hours, the water quality deterioration rate was significantly accelerated. The correlation analysis of the deterioration of water quality parameters shows that, the deeper the depth of cut-off pipeline is, the less the water disturbed by the main pipe is and the higher the correlation level of each parameter is.
What problem does this paper attempt to address?