Power Electronic Transformer Using Multi-Pulse Rectification Technique

ZHU Ming-lei,ZHAO Rong-xiang,YANG Huan
DOI: https://doi.org/10.3785/j.issn.1008-973x.2017.09.021
2017-01-01
Abstract:A novel topology of power electronic transformer (PET) with no high voltage direct-current (DC) bus capacitors was investigated,aiming to solve low reliability and high cost problems of high voltage DC bus capacitors in PET.Compared with traditional PET topologies,the harmonic eliminating of input current was implemented by multi-pulse rectifiers (MPR) in the proposed topology,and the problem of cost and reliability caused by high voltage DC bus capacitors were eliminated.Because of the cancellation of high-voltage DC bus capacitors,its flexible grid connection was implemented with no charge resistance,and the voltage balancing control effect of each DC bus was improved.The effectiveness of DC bus voltage balancing,harmonic eliminating and flexible grid connection with the proposed PET was verified by simulation of Matlab/Simulink and experimental results from prototype of 6 kV and 100 kVA.