PD development law and diagnostic methods of typical insulation defects in SF6 gas-insulated switchgear

Dapeng Duan,Yanqing Wang,Yang Jiang,Gehao Sheng,Wei Li
DOI: https://doi.org/10.3969/j.issn.1001-1390.2017.08.021
2017-01-01
Abstract:In China, the voltage class of 110 kV or above 110 kV of the transmission grid mainly adopts SF6 gas insulated switchgear (GIS) equipment, and especially that the application of GIS equipment in the power grid is more and more widely.With the improvement of voltage level and system capacity,the internal insulation faults SF6 switchgear equipment in the power grid probability tend to rise, thus equipment defect and state judgment are one of the key problems to be solved.Aiming at this problem, this paper mainly studies the typical defects development mechanism in SF6 gas insulated switchgear equipment and signal characteristics of different stages of development, focusing on detection methods of SF6 switchgear partial discharge based on the ultra high frequency and acoustic emission detection, and conduct some tests and researches about the typical defects discharge of GIS and the development process.Finally, the characteristic spectrum development law and diagnostic methods were proposed, and a typical case of GIS partial discharge is analyzed and verified.