Suppression of Circulating Current Caused by Multiple DG Negative Pole Ground Fault in DC Microgrid Based on Control With Two Degrees of Freedom
ZHANG Yong,XIA Yanghong,ZHU Jie,ZHAO He,YU Miao,WEI Wei
DOI: https://doi.org/10.13335/j.1000-3673.pst.2018.0241
2018-01-01
Abstract:To effectively solve energy crisis and environmental pollution, DC microgrid grasps more and more attention, into which renewable energy is integrated mainly with parallel H-bridge DC/DC converters. But DGs are generally installed outdoor, and the lines are prone to age, resulting in poor insulation. Thus, there often appears DG ground fault, especially in thunderstorm weather, causing large common ground circulating current among some converters, triggering overcurrent protection of the converter and affecting system stability. Focusing on this problem, a control strategy with two degrees of freedom is proposed to suppress common ground circulating current, thereby increasing fault ride-through capability. The control strategy remains effective in both normal operation and faulty condition, hence the cost is not affected even under faults. Specifically, firstly it is proven that conventional bipolar modulation control cannot suppress the described circulating current. Then, a control method with two degrees of freedom is proposed, meaning that the common mode-based control can suppress the common ground circulating current, and droop-based control can improve current sharing precision among the converters. Inertial element is added to help voltage recovery. Finally, simulation and experimental results are presented to verify the effectiveness of the proposed method.