PCC Voltage Power Quality Restoring Strategy Based on the Droop Controlled Grid‐connecting Microgrid

Wei Feng,Kai Sun,Yajuan Guan,Josep M. Guerrero,Xi Xiao
DOI: https://doi.org/10.1049/joe.2017.0561
2017-01-01
The Journal of Engineering
Abstract:: As the non-linear loads increase along the low-voltage distribution network (LVDN), voltage harmonic components will appear at the point of common coupling (PCC). To improve the voltage power quality of PCC, an active PCC voltage power quality restoring strategy based on droop controlled grid-connecting microgrid (DCGCM) is proposed. The load current of LVDN and the grid-connecting current of DCGCM are sampled and are calculated through an additional PCC voltage restoring controller adopted in the secondary level of system. Then, the generated voltage harmonic reference offset is sent to the primary level and tracked by voltage controlled inverter. In this way, the required harmonic current is injected into the LVDN to supply the nonlinear loads at the cost of slight voltage distortion of DCGCM ’ s output voltage. Therefore, the voltage power quality of PCC can be restored. At last, the simulation results from SIMULINK/MATLAB have been presented to verify the validity of the proposed control strategy.