Comments on Fault Handling and Protection Technology for VSC-HVDC Transmission Lines

LIU Jian,TAI Nengling,FAN Chunj u,HUANG Wentao
DOI: https://doi.org/10.7500/AEPS20150125002
2015-01-01
Abstract:Owing to the specific mode of regulation and structure of the voltage source converter-high voltage direct current (VSC-HVDC) transmission system,the DC line fault current is characterized by high increasing speed and great peak value. This is extremely susceptible to destruction of converter devices and damage to insulation of equipment.VSC-HVDC system cannot realize fault self-clearing by adjusting the firing angle.Therefore,higher requirements are made on protection and fault handling of DC transmission lines.For DC line faults,not only is reliable and fast protection needed for fault identification,but also corresponding control measures and circuit should be taken to limit the fault current and reduce the damage of the current to converter devices,the DC line itself and system.Based on the fault characteristics of VSC-HVDC transmission lines,the state of the art of DC line protection technology and prospects for application at home and abroad are described.Protection and fault handling technologies of DC lines are summarized and analyzed with respect to fault current limiting,reducing fault impact,and protection principle. The fault handling capability of several protection circuits, converter topologies, DC transmission structures and DC breakers are focused on.Finally,several key issues about protection and fault handling of VSC-HVDC transmission lines and future directions for further research demanding prompt solution are discussed.
What problem does this paper attempt to address?