Transient Relay Protection Criterion for EHV Transmission Line with SCC

LIU Yu,TAI Neng-ling,FAN Chun-ju,YU Zhong-an,MENG Xiao
DOI: https://doi.org/10.3969/j.issn.1003-8930.2014.03.001
2014-01-01
Abstract:Series Capacitor Compensator(SCC)can increase transfer capability in Extra High Voltage(EHV)power system,but it can cause mal-operation of traditional relay protections. In this paper,the wave process theory and the frequency response theory are applied to analyze the frequency domain property of transient current at different fault positions in EHV transmission line with SCC. In addition,wavelet transform is used to extract high-frequency and secondary high-frequency components. Also,the differences between energy integration ratio and energy ratio of these two components are demonstrated,and energy integration ratio is chosen as the protection criterion. Testing results suggest that this criterion can correctly operate on different fault and system situations,and increases reliability and sensitivity of relay protection.