Loop Type Conversion and Regulation of Line Flow Violation Based on Loop Analysis

WANG Cheng-min,JIANG Chuan-wen,HUANG Rui
DOI: https://doi.org/10.3969/j.issn.1003-3076.2005.03.009
2005-01-01
Abstract:Node voltage and loop current functions of electric power network are established on the base of equivalent π-model network, with loads equivalent to a voltage source and impedance branches to the link branches and grounding branches to the tree branches, in order to expand the power flow equations as node voltage formulas with loop current formulas and to express the Jacob matrix as function with node voltage and loop current variables; in addition, the loop type and Qθ node type are defined. The loop and node types are transformed so as to regulate the injected nodal active powers and to control the line flow which limit is violated. The case study is made at IEEE-30 system and the better effect is proved.
What problem does this paper attempt to address?