Co-combustion of sludge in a 100 MW unit coal-fired boiler:numerical simulation

Libao YIN,Tianyu ZHU,Cheng ZHANG,Qingyan FANG,Qisheng XU,Gang CHEN
DOI: https://doi.org/10.3969/j.issn.1002-3364.2015.03.028
2015-01-01
Abstract:Numerical simulation using single-and double-mixture-fraction /PDF (Probability Density Function) transport model was carried out to evaluate the characteristics of coal burning alone and with domestic sludge on a 420 t/h tangentially coal-fired boiler.The flow,combustion and NOx emission properties were investigated.The sim-ulation results were consistent with the field test under the same working condition,when the coal was burned alone and the load is 70% and 1 00%.Under 1 00% load condition,the NOx emission reduced after co-combustion.With the increasing mass ratio of sludge,the burn out rate of coal decreased slightly.Temperature distribution and flue gas composition distribution in the furnace were roughly the same.All these above indicated that the co-combustion had little influence on characteristics of flow,combustion and NOx emission of this boiler.
What problem does this paper attempt to address?