Study on Sub-synchronous Oscillation Mechanism and Suppression Measures for Direct Drive Generators in Direct-current Vicinity

Haifeng QIU,Xinjun DING,Ziming LI,Weiqing WANG
DOI: https://doi.org/10.14044/j.1674-1757.pcrpc.2018.03.028
2018-01-01
Abstract:For the frequent sub-synchronous oscillation (SSO) phenomena in the grid connection from the transmission end of direct drive permanent magnet wind turbine generators (D-PMSGs) based wind farms in direct-current vicinity of Hami area,in this paper,the equivalent model of wind power interconnection including multiple direct drive permanent magnet wind turbine generators (D-PMSGs) is set up,the equiv-alent model and mechanism of the D-PMSGs to the sub-synchronous oscillation are studied. Then,the is-sue of sub synchronous oscillation due to interaction of both D-PMSGs and weak AC system is studied by the use of eigenvalue analysis method. After that,the influence of such factors as system impedance,wind power output,number and control parameters of D-PMSGs etc.,on the feature of wind power sub synchro-nous oscillation is simulated and analyzed. It is shown by the simulation result that in case of interconnec-tion of the D-PMSGs by the weak transmission line,its ineraction with the weak AC system generates a pair of characteristic root with weak impedance,of which the real part is positive,showing that sub-syn-chronous oscillation mode is instable. Multiple influence factors have different effects on the SSO character-istics of wind farm. Finally,the suppression effect of SVG additional damping control on sub-synchronous harmonic is preliminarily verified by real time digital simulation experiment.
What problem does this paper attempt to address?