Study on Comparison of Two Methods of Passive Three-phase Power Factor Correction

SHI Jian-jiang,ZHANG Jian-guo
DOI: https://doi.org/10.3969/j.issn.1000-100x.2005.02.016
IF: 5.967
2005-01-01
IEEE Transactions on Power Electronics
Abstract:Aiming at the actuality that the extensive application of power electronics results in serious harmonic pollution and aeronautical power supplies demand on high reliability,the passive three-phase power factor correction have been applied in the aeronautical power supplies.There are two methods of the passive three-phase power factor correction:the first one is that the filter capacitors and inductors are applied in the input-end of alternating current,and the second one is that the filter capacitors and inductors are applied in the output-end of three-phase rectifier.The advantages and drawbacks of the two methods of the passive three-phase power factor correction aer concluded in this paper through simulation and analysis and verified by experiment.To reduce the voltage stress of power switching transistors,the second method of power factor correction was applied in aeronautical power supply.