Abstract:Conventional undervoltage load shedding (UVLS), which executes load shedding round by round, adopts constant time delay of every round, thus failing to adapt with the change of load characteristics. This paper employs the equivalent susceptance variation of the load to estimate the transient voltage security. Furthermore, this paper selects the load nodes with lower transient voltage security as the weak nodes and then shortens the time delay of the weak nodes in order to recover the load voltage quickly, thus proposing a UVLS control scheme based on transient voltage security assessment. Simulation results on IEEE 39-bus system have proved that the modified UVLS can adapt with the load characteristics and decrease the load curtailments when the load voltage recovers quickly, which reduces the economic loss caused by undervoltage load shedding.