A combined deloading method based on the underfrequency and undervoltage relay

Ye LI,Baohui ZHANG,Zhiqian BO
2015-01-01
Abstract:Conventional undervoltage load shedding (UVLS) and underfrequency load shedding (UFLS), designed separately without considerations of the load characters and mutual influences of the voltage and the frequency, may result in excessive or insufficient load curtailments. This paper proposes a combined deloading method based on the underfrequency and undervoltage relay. This method uses the real-time measured local responses of the frequency and the voltage to calculate the proportion of UVLS and the accessional proportion of UFLS adaptively with considerations of the influences of frequency and voltage dynamics on the load active power. Furthermore, this method adopts the larger proportion between the proportion of UVLS and UFLS as the practical load shedding proportion, and then transmits the practical load shedding proportion to the underfrequency and undervoltage relay, thus triggering local successive load shedding. Simulation results of IEEE 39-bus system have proved that the new method, compared with the conventional one, can adapt better to load characters and disturbance types, thus protecting the power system from frequency and voltage instabilities more effectively.