Research on a New Monitoring Method of tanδ with Low Cost and High Precision

陈天翔,张保会,陈天韬,刘军虎,张翰森
DOI: https://doi.org/10.3969/j.issn.1003-6520.2005.01.017
2005-01-01
Abstract:By analysis of the operating principle of micr o current sensor and the deficiency of Zero-flux micro current sensor, a new me thod of on-line monitoring of tanδ is presented, which is based on balance principle of QSI Schering bridge. Using passive micro current sensor as balance current tester, the system calculates the phase differences by a MCU computer. The techniques of anti environmental interference and intelligent monitoring are applied to enable the theoretical resolution of tanδ to reach to 6.9×10 -5 . The on site tests show that the system is with capabilities of high ant i interference and high precision in monitoring.
What problem does this paper attempt to address?