Experimental Analysis on Breaking Performance of ACB

Juwen DING,Yi WU,Chunping NIU,Delong DONG,Fei YANG,Mingzhe RONG
DOI: https://doi.org/10.3969/j.issn.1001-5531.2015.11.001
2015-01-01
Abstract:For a certain arc extinguishing system of an air circuit breaker (ACB),the experiments were performed by means of fuse blown with the adoption of a single-frequency LC oscillator circuit to verify each influencing factor on breaking capacity.The experimental results show that arcing voltage can be notably enhanced by changing the material and installation location of innermost filter in the vent,and increasing the distance between arc chute and movable contacts.The schemes based on experimental studies were then proposed to improve the switching performance of an ACB.
What problem does this paper attempt to address?