Mass transfer coefficient for liquid dehumidification based on vapor pressure difference

Runxia ZHANG,Zanshe WANG,Xiangzhao MENG,Fang WANG,Fengrong LIU,Zhaolin GU
DOI: https://doi.org/10.11949/j.issn.0438-1157.20150681
2015-01-01
Abstract:The influencing factors for mass transfer of gas-liquid interface in liquid desiccant system are analyzed. A mass transfer correlation is given in dimensionless form based on the driving force of mass transfer, which is the vapor pressure difference through gas-liquid interface. The constants in the correlation are fitted based on published experimental data of LiCl-H2O-air system in a column packed with cross corrugated cellulose. Another group of published experimental data of LiCl-H2O-air system in a column packed with polyvinyl chloride is used for validating the correlation, with the relative deviation between experimental and calculated results from-10.48% to 5.28%. Moreover, a liquid dehumidification system driven by heat pump is set up, with LiBr-H2O as desiccant and finned tube heat exchanger as packings, and the experimental data are used for validating the correlation. The result shows that the deviation is-1.8%—12.8%. All these results show that the correlation has a high accuracy for mass transfer coefficient prediction in liquid dehumidifier with structured packings.
What problem does this paper attempt to address?