Comparison of Chinese and foreign standards for foam extinguishing agents

Si-bo FU,Jing-lei CAI,Ping XU,Zhi-li ZHANG,Hong-peng SHI
DOI: https://doi.org/10.3969/j.issn.1009-2455.2018.02.019
2018-01-01
Abstract:Based on the introduction of the research and development of foam extinguishing agents, a com-parison among GB 27897—2011 Class A Foam Extinguishing Agents, NFPA standard of USA, GB 15308—2006 Foam Extinguishing A gents, and ISO standard was carried out. The study found that both national standard and ISO standard included the following indexes: antifreezing performance, melting property, sediment, specific fluid-ity, pH value, tensile force, diffusion coefficient, foam expansion, drainage time and so on; and the relevant test methods and requirements of them were basically the same. However, compared to NFPA standard, national standard was lack of the control indexes about environmental implication, which was just considered from aspects of fire extinguishing and deposit, with freezing point, antifreezing performance, melting property, specific fluidity, corrosivity, pH value, surface tension, wettability, drainage time, thermal insulation barrier property, and some other indexes set up as well; besides, the requirement about temperature and mixing ratio of samples during the test in the mentioned two standards were also different. Therefore, it was suggested that, national standard should take NFPA as reference and further complete toxicology and some other related indexes as well.
What problem does this paper attempt to address?