Comparative analysis of heat transfer performance of the smooth U-tube and finned U-tube in ground source heat pump

Mei SU,Ji-xiang YIN,Jun WANG
DOI: https://doi.org/10.3969/j.issn.1005-9954.2017.11.007
2017-01-01
Chemical engineering
Abstract:A smooth U-tube and internal longitudinal finned U-tube model were established in practical size respectively.Then the heat transfer performance of the two heat exchangers was simulated by FLUENT software.The effects of inlet flow velocity,inlet temperature,drilling depth and thermal conductivity of backfill materials on the heat transfer performance of the two heat exchangers were investigated.The results show that the increase of flow velocity and the decrease of drilling depth can improve the heat transfer performance of finned U-tube geothermal heat exchanger (GHE) more significantly,while the increase of inlet temperature and conductivity of backfill material has almost the same effect on heat transfer rate per unit depth of the two types of heat exchangers.Increasing the length and width of the fins can effectively improve the heat transferperformance.The purpose of this paper is to provide the basis for the heat transfer enhancement of the heat exchanger.
What problem does this paper attempt to address?