Field Research on Operating Performance of Air Source Heat Pump under Low Temperature Conditions in Beijing

Xiaoxia BAI,Yuying SUN,Wei WANG,Jingdong LIU,Xu WU
DOI: https://doi.org/10.13614/j.cnki.11-1962/tu.2017.10.09
2017-01-01
Building Science
Abstract:To further reveal actual operating performance of Air Source Heat Pump (ASHP) and obtain operating characteristics under low-temperature conditions,a 80-day field test was conducted during the heating season from 2015 to 2016 in Beijing.The operating performance of the ASHP is analyzed,especially in the 3 coldest days.The test results indicate that average heating capacity,daily energy consumption and COP are 15.2 kW,0.56 kW·h/m2 and 2.77 respectively during the test.Under low-temperature conditions,ambient temperature fluctuate from-15.2 ℃ to-5.1 ℃,the average discharge temperature of the ASHP is 118.5 ℃ with the maximum up to 124 ℃ and the duration of 25% for temperature over 120 ℃;the average of compression ratio is 11 with a maximum up to 11.8;heating capacity is 10.7kW in average with minimum down to 8.8 kW which declined by 55%.Meanwhile,the mean value of COP is 1.96 with a minimum down to 1.49.These results lay a necessary and practical foundation for understanding the actual operation performance of ASHP and its operating characteristics under lowtemperature conditions.