Running performance of low-temperature air-source heat pump applied in winter of Beijing

Ai By,Chengbin Wu,Wenxing Shi,Songlin Zhai
2015-01-01
Abstract:Tests an air-source heat pump with a compensating scroll compressor of quasi two-stage compression in an office building of Beijing during nearly the whole heating season of 2013.By analysing the heating capacity,energy consumption and other performance parameters,concludes that the air-source heat pump has been running steadily during the testing period,and the average temperature of supply water is 42.0 ℃,and heating seasonal performance factor (HSPF)is about 3.20 kWh/kWh.The coefficient of performance can remain more than 2.8 kWh/kWh when outdoor temperature is -8 ℃,which proves that the air-source heat pump with scroll compressor of quasi two-stage compression shows good running performance as heating device in Beijing.