Mechanically Pump-Driven Separate Heat Pipe Employed in Air Conditioning System for Cooling Energy Recovery

Zhen-jiang GUO,Jie SHAO,Wei WANG,Xiao-hua LI,Xiao-liang TIAN
DOI: https://doi.org/10.3969/j.issn.1673-7237.2016.03.003
2016-01-01
Abstract:To experimentally investigate the cooling energy recovering capacity of mechanically pump-driven separate heat pipe (MPSHP) in the air conditioning system, four MDSHPs were constructed and filled into R134a as working fluid. When the MPSHP increased from 0 to 4 at the constant inlet air state of 28.5 ℃ and 60% relative humidity, the apparatus dew point fell from 11.7 ℃ to 8.2 ℃, and the air -supply temperature rose from 11.7 ℃ to 24.1 ℃ , while dehumidifying capacity of the system has ultimately increased by 29.5%. The index δ (ratio between the cooling energy saved by MPSHPs and the cooling capacity of the air conditioner’s evaporator) is 66.0%. The study indicates that the air conditioning system can significantly reduce its energy consumption and improve its dehumidifying capacity when MPSHPs are employed in the air-conditioning process.
What problem does this paper attempt to address?