Experimental Study on Charging Performance of Cool Storage Air-conditioning System with Separate-type Heat Pipe

Fang Guiyin,Zhang Man,Wu Shuangmao,Liu Xu
DOI: https://doi.org/10.3969/j.issn.0253-4339.2009.04.046
2009-01-01
Abstract:The principle of cool storage air-conditioning systems with separate-type heat pipes was stated.An experimental apparatus was built and the experiment on charging performance of a cool storage air-conditioning system with separate-type heat pipes was conducted.The test results indicate that the system could operate steadily and the coefficient of performance was from 2.6 to 3.8.The ice packing factor could reach 55% and the cool storage capacity increased linearly with time approximately.The medium pressure in the heat pipe was from 0.4MPa to 0.3MPa and the medium temperature at the heat pipe inlet was from-10℃ to-12℃.In addition, the difference between the inlet medium temperature and the outlet medium temperature decreased gradually during the cool storage process.