Energy-Saving Operation Modes for a Heat Recovery Unit in Office Building

Shu-fang SUN,Guo-yuan MA,Feng ZHOU
DOI: https://doi.org/10.3969/j.issn.1673-7237.2016.06.025
2016-01-01
Abstract:The current proportion of fresh air load in the building energy consumption is very large, and heat recovery can effectively reduce fresh air load. It is important to analyze the annual operation of heat recovery units in air conditionings in detail in order to improve the running situation. For an office building in Beijing, the heat pipe heat recovery unit developed by the research group was adopted in the air conditioning system. The office building model was set up with DeST software, which was designed for building energy consumption by Tsinghua University. The two fan-coil and fresh air system was used for the air conditioning. The balance temperature was introduced for dividing the annual on-off time period and the operation mode for the heat recovery unit. The heat recovery figure was drawn according to the atmosphere data. The heat transfer rate was obtained for different operation modes. The fresh air load could be saved by 62.6%to 66%, and the energy efficiency was obvious.
What problem does this paper attempt to address?