Numerical analysis on mechanical smoke exhaust at smoke vent in lateral smoke extraction system

杨娟,潘旭海,汪志雷,华敏,蒋军成
DOI: https://doi.org/10.3969/j.issn.1009-0029.2017.03.010
2017-01-01
Fire Science and Technology
Abstract:FDS was used to research the lateral smoke extraction system in road tunnel and the temperature of smoke layer interface was calculated by the N-percentage method.The plug holing phenomenon in fire was researched too.The changing of temperature,depression of smoke layer and mass fraction of carbon monoxide near the smoke vent were investigated to study the efficiency of the mechanical smoke exhaust in lateral smoke extraction system.Results showed that an appropriate increase in the amount of volumetric flow rate can exhaust smoke rapidly and decrease the temperature in the ceiling,however,may cause the plug holing phenomenon and lead to reduction of exhaust effect.The smoke should cover half of the smoke vent and the volumetric flow rate of a single smoke vent should range from 4.5 m/s to 6.0 m/s,to get better exhaust effect.
What problem does this paper attempt to address?