Non-Linear Analysis on Allowed Maximal Length of Frame Structures

Aihui ZHANG,Zhenda PAN,Jianguo TONG
DOI: https://doi.org/10.3969/j.issn.1005-0159.2010.04.006
2010-01-01
Abstract:The length of 1 000 MW power plant main building is usually 100 m or longer,and the expansion joint is not allowed due to the production process,so that the building becomes an over-long structure.The allowed maximal length of RC frame structure based on existing code and guideline is determined by experience or elastic analysis.In this paper,taking the length of the structure unit as the variable,the non-linear analysis of over-long RC frame structures was conducted based on an under construction power plant.A model was built to analyze the width of the cracks,and the allowed maximal length of the structure unit was discussed based on the allowed maximal crack width at serviceability limit state.
What problem does this paper attempt to address?