Experimental Test and Comparison of Flare Flame Monitoring Technology

Yong-zhong BAI,Jie-dong ZHANG,Wen-yi DANG,An-feng YU,Jun-cheng JIANG
DOI: https://doi.org/10.11731/j.issn.1673-193x.2013.06.026
2013-01-01
Abstract:The response signals of thermocouple monitoring system,ultraviolet monitoring system and flame ionization monitoring system were tested and analyzed using Data Acquisition(DAQ) card and Labview software.Results showed that the response time of thermocouple monitoring system is 1.5-3min,and the response time of ultraviolet monitoring system is 2-4s,but its output voltage is smaller,and could not distinguish the pilot flame from the high level igniter flame.The response time of flame ionization monitoring system is 2-6s and its output signal is strong enough to detect the flame in a short time.
What problem does this paper attempt to address?