AN INDOOR AIR QUALITY WIRELESS MONITORING NETWORK WITHA CARBON DIOXIDE PREDICTION MODEL

Sy-Yuan Kang,Chao-Heng Tseng,Ai-Jie Wang,Yi-Hsuan Shih,Nhat-Thien Nguyen
2016-01-01
Fresenius environmental bulletin
Abstract:In this study, a wireless air quality monitoring network was developed, and a field study was conducted at three sites at the National Taipei University of Technology. The network uses CO2, temperature, and relative humidity sensors and ZigBee wireless monitoring software. System validation included laboratory calibration for measurement errors, comparisons of live and direct readings of the devices, and the establishment of a CO2 concentration balance prediction model. This monitoring system can estimate the exchange values of indoor and outdoor spaces and verify the feasibility of prediction models. At the three sites, the average indoor in/out air exchange rate obtained using a ZG01 gas sensor were 17.21, 17.22, and 14.02 m(3)/min, and those obtained using an AZ7722 gas sensor were 16.36, 18.88, and 11.66 m(3)/min. According to the CO2 concentration prediction model, the maximum number of people allowed at the three sites was 17, 18, and 12 in offices A, B, and C, respectively. When these numbers are exceeded, the CO2 concentration is likely to be higher than the recommended concentration of 1000 ppm. Furthermore, the effect of increasing the number of in/out air exchange fans on the indoor CO2 levels was assessed. According to the model predictions, installing one and two in/out air exchange fans reduces the indoor CO2 concentration by 10.4% and 17.3%, respectively.
What problem does this paper attempt to address?