Research of non steady state error control strategy of bus voltage and frequency in micro grid system
Yongdong Li,Yongliu Xie,Zhijiang Cheng,Xiaochao Fan,Bo Dong,Lin Qiu
DOI: https://doi.org/10.15938/j.emc.2016.07.007
2016-01-01
Abstract:When the micro-grid system is running in islanding mode ,it’ s disconnected from external pow-er because of the grid failure .In this case,the AC bus voltage and frequency of micro-grid system need to use droop control due to the loss of support from the grid .As the steady state error problems of voltage and frequency problems exist in the traditional droop control ,the influence of the control parameters of the mi-cro-grid system inverter output impedance was analyzed ,and the method of the system's output impedance for inductive was studied .Based on the above studies ,a control method to eliminate voltage and frequency steady state error problem without communication line was put forward ,and the impact on system stability by droop factor was analyzed .Finally ,simulations and experiments control method was validated .The sim-ulation results show drooping curve translational approach reduces the static error , active-frequency and reactive-voltage sag vertical curve shift ,significant fluctuations do not occur ,and in accordance with the proportion set droop coefficient reasonable allocation;sudden load increases from 680 W to 1 050 W,and then suddenly reduced from 1 050 W to 680 W,and two inverter output current quickly meets the load re-quirements of mutation , and mutation on load bus voltageis is smaller .The results show the correctness and feasibility of the control method ,and provide theoretical and experimental guidance for stable opera-tion of microgrids .