A Control Strategy of Islanded Microgrid With Nonlinear Load for Harmonic Suppression

Qiang Chen
DOI: https://doi.org/10.1109/access.2021.3064413
IF: 3.9
2021-01-01
IEEE Access
Abstract:A control strategy of islanded microgrid is proposed in this paper against the harmonic circulation of the inverters and the Point of Common Coupling (PCC) voltage harmonic distortion of the microgrid caused by nonlinear load. The reference voltage of the inverter's outer voltage loop is given by the decoupling control of the fundamental and harmonic components. Virtual synchronous generator (VSG) is adopted in fundamental domain. In harmonic domain, adaptive harmonic compensation and harmonic virtual impedance are applied to obtain the harmonic components of the reference voltage of the outer voltage loop. The hybrid control strategy combining P control and repetitive control in parallel is adopted in the outer voltage loop. Multi-period repetitive control (MPRC) with fast repetitive control (FRC) is adopted to improve the tracking control performance of the main harmonic components of the given reference voltage. Fractional order delay approximated by Lagrange interpolation polynomial FIR filter is applied in MPRC for different repetitive control periods at the fixed sampling period. The output harmonic current of the inverters can be distributed autonomously according to the capacity of the inverters to suppress the harmonic circulation, and the suppression of the PCC voltage harmonic distortion is realized. Simulation based on Matlab/Simulink and hardware-in-loop(HIL) test are carried out, and the results show that the proposed control strategy is effective.
computer science, information systems,telecommunications,engineering, electrical & electronic
What problem does this paper attempt to address?
The problems that this paper attempts to solve are the harmonic circulating flow between inverters and the harmonic distortion of the Point of Common Coupling (PCC) voltage in islanded micro - grids due to non - linear loads. These problems will affect the stable operation of inverters and even damage the equipment. Moreover, when the PCC voltage harmonic is severe, it will affect the normal operation of electrical equipment within the micro - grid. Therefore, the paper proposes a control strategy to suppress these harmonic problems and ensure the power quality of the micro - grid. Specifically, the paper proposes a control strategy for islanded micro - grids, aiming to solve the following two main problems: 1. **Harmonic circulating flow between inverters**: Non - linear loads will cause the circulating flow of harmonic currents between inverters, which will affect the stable operation of inverters and may even lead to equipment damage. 2. **Harmonic distortion of PCC voltage**: Non - linear loads will also cause the harmonic distortion of PCC voltage, affecting the power quality within the micro - grid. To solve these problems, the paper proposes a new control strategy, which is achieved through the following aspects: - **Decoupling control of fundamental and harmonic components**: By decoupling the control of fundamental and harmonic components, the fundamental and harmonic components of the reference voltage of the outer voltage loop of the inverter are obtained respectively. - **Virtual Synchronous Generator (VSG) control**: In the fundamental frequency domain, VSG control is adopted to simulate the rotor motion and stator excitation regulation characteristics of synchronous generators, making the frequency and voltage regulation characteristics of inverters close to those of synchronous generators. - **Adaptive harmonic compensation and virtual impedance**: In the harmonic domain, adaptive harmonic compensation and virtual impedance control are combined to obtain the harmonic component of the reference voltage of the outer voltage loop. - **Hybrid control strategy**: In the outer voltage loop, a hybrid control strategy combining P - control and repetitive control is adopted to improve the tracking control performance of the given reference voltage harmonic component. Through these methods, the paper aims to effectively suppress the harmonic circulating flow between inverters and the harmonic distortion of PCC voltage, thereby improving the stable operation ability and power quality of islanded micro - grids.