Main Circuit Configuration Selection of D-STATCOM Used for Large Unbalanced Load Compensation

ZHU Yong-qiang,SONG Qiang,LIU Wen-hua,LI Jian-guo,XU Shu-kai
DOI: https://doi.org/10.3321/j.issn:1000-1026.2005.07.012
2005-01-01
Abstract:For D-STATCOM used for large unbalanced load compensation, the criteria for selection are proposed, such as fitness for high voltage large capacities, capability of phase by phase compensation and convenience in redundancy design. Several kinds of main circuit configurations are described. Judged by the special requirements on compensation devices for large unbalanced loads, the latter part of the paper gives a detailed description of the configuration with isolating transformer. The equivalent circuit and mathematical model for the configuration, magnetic path design and radiating equivalent circuit of the isolating transformer, the DC voltage wave of different capacitors connections, PWM control based on carrier waves shift for harmonic restriction, etc. are discussed. The characteristics of the configuration with isolating transformer are summarized.