Hardware-in-the-Loop and Field Validation of a Rotor-Side Subsynchronous Damping Controller for a Series Compensated DFIG System

Jan Shair,Xiaorong Xie,Yunhong Li,Vladimir Terzija
DOI: https://doi.org/10.1109/tpwrd.2020.2989475
IF: 4.825
2021-01-01
IEEE Transactions on Power Delivery
Abstract:In the past decade, several subsynchronous control interaction (SSCI) incidents have been reported in various large-scale grid-interfaced doubly-fed induction generator (DFIG) based wind farms. The subsynchronous oscillation caused by the SSCI endangers the safe and reliable operation of wind power systems. The DFIG's converter controls play a crucial role in such interactions; therefore, several SSCI mitigation schemes have been reported, which modify the DFIG's converter controls to stabilize the subsynchronous oscillation caused by the SSCI. However, the effectiveness of such converter control modifications has not been verified through laboratory or field experiments. This paper considers a practical rotor-side subsynchronous damping controller (RSDC) and fills the gap by first validating the RSDC's performance through controller hardware-in-the-loop (CHIL) simulations, and then implementing it in a real-world DFIG connected to a series compensated line. The RSDC fundamentally reshapes the effective impedance of the DFIG to stabilize the subsynchronous oscillation. The CHIL simulations, as well as the field tests, successfully validated the RSDC's ability to suppress the SSCI. The results enhanced the practical confidence of the SSCI mitigation strategy based on RSC's converter control modification.
What problem does this paper attempt to address?