A Criterion for Accurate Identification of Commutation Failure in HVDC Systems

Zhanhong Wei,Wanliang Fang,Jun Liu
DOI: https://doi.org/10.1016/j.epsr.2020.106338
IF: 3.818
2020-01-01
Electric Power Systems Research
Abstract:Commutation failures (CFs) caused by AC faults are the most frequent and adverse events in HVDC systems. Accurately confirming CFs has great significance in guaranteeing the safety and stability of AC/DC power systems. The requirements of CF criteria are as follows: not only can whether CF occurs be judged but also the beginning and ending instants can be accurately determined. For the problem that a CF cannot be accurately determined in an electromagnetic transient (EMT) simulation of an HVDC system, in this paper, based on further investigation of commutation processes and CF mechanisms, an AC-DC current criterion (ADCC) is proposed to accurately identify single, double and successive CFs in HVDC systems. The ADCC is derived from Kirchhoff's current/voltage law and is based on the DC current and the valve-side AC current. Detailed explanations and justifications are given that are strictly proven. Moreover, for the convenience of studying CF problem, a method is presented to quickly determine the valves that suffer CF. The validity and accuracy of the ADCC are also demonstrated through EMT simulations under different scenarios, and the bridge arm short circuit phenomenon verifies the accuracy of the criteria. Compared with the ADCC, the applicability of existing CF criteria is reexamined.
What problem does this paper attempt to address?