Experimental Study of Heat Transfer Capacity for Loop Heat Pipe with Flat Disk Evaporator

Zikang Zhang,Hao Zhang,Zhenyuan Ma,Zhichun Liu,Wei Liu
DOI: https://doi.org/10.1016/j.applthermaleng.2020.115183
IF: 6.4
2020-01-01
Applied Thermal Engineering
Abstract:Loop heat pipes are passive heat transfer devices which can meet the heat dissipation requirement of high-power electronic devices in aerospace and terrestrial applications. This paper investigates the operating characteristic of a stainless steel-ammonia loop heat pipe with a flat disk evaporator. A biporous wick made from sintered nickel powders was used to produce the capillary force. The heat transfer distance was 1.6 m and the allowable heater surface temperature was below 70 degrees C. Tests demonstrated that the loop could operate under a heat load ranging from 2.5 W to 180 W (heat flux 0.15-10.8 W/cm(2)) at heat sink temperature of -10 degrees C. In addition, variable conductance mode and constant conductance mode existed, and no obvious temperature overshoot or pulsation was observed. The evaporator inlet temperature went through a staged decline due to the effect of initial driving force of vapor expansion during the start-up process. Meanwhile, under the synergy of heat leaks from heater surface and long transport line, whether the vapor phase would form inside the compensation chamber could result in a large discrepancy in temperature trends. The minimum evaporator thermal resistance was 0.096 degrees C/W at heat sink temperature of -10 degrees C and the minimum LHP thermal resistance was 0.252 degrees C/W at heat sink temperature of 10 degrees C.
What problem does this paper attempt to address?