Influence of air-conditioning systems on buoyancy driven air infiltration in large space buildings: A case study of a railway station

Xiaochen Liu,Xiaohua Liu,Tao Zhang
DOI: https://doi.org/10.1016/j.enbuild.2020.109781
IF: 7.201
2020-01-01
Energy and Buildings
Abstract:Large space buildings are widespread nowadays in the metropolis, in which the buoyancy driven air infiltration is extremely severe in heating/cooling seasons. This study pointed out that air-conditioning systems have a notable influence on air infiltration in large space buildings. A CFD model of a railway station was established and installed with typical air-conditioning systems, i.e., mixing ventilation (MV), displacement ventilation (DV), and radiant floor with displacement ventilation (RF+DV). Air infiltration rates of these cases were compared when the operative temperatures in the occupant zone were the same, respectively in the heating/cooling conditions. It is indicated that a uniform vertical temperature distribution in the heating condition and a significant thermal stratification in the cooling condition are potential to reduce air infiltration rate, which is best corresponded by RF+DV. Compared with the commonly-used stratified air-conditioning system with MV, RF+DV can reduce the air infiltration rate from 0.68 h(-1) to 0.53 h(-1) in the heating condition and save 38% of the heating capacity; it can reduce the air infiltration rate from 0.49 h(-1) to 0.33 h(-1) in the cooling condition and save 23% of the cooling capacity. (C) 2020 Elsevier B.V. All rights reserved.