Frequency-Coupling Admittance Modeling of Converter-Based Wind Turbine Generators and the Control-Hardware-in-the-Loop Validation

Wei Liu,Xiaorong Xie,Xu Zhang,Xuan Li
DOI: https://doi.org/10.1109/tec.2019.2940076
IF: 4.8767
2019-01-01
IEEE Transactions on Energy Conversion
Abstract:Recently, sub- and super-synchronous oscillation (SSO) associated with converter-based wind turbine generators (WTGs) has been attracting wide attentions. To investigate such SSO incidents, impedance or admittance-based modeling and analysis were widely used. It was discovered that coupling effects exist between impedances or admittances at complementary (i.e., sub and super-synchronous) frequencies. However, there is a lack of experimental validation on the coupling effects of different WTGs. In this paper, the frequency-coupling admittance models (FCAMs) of two types of widely adopted WTGs, i.e., direct-drive and doubly-fed WTGs, are presented at first. Secondly, a perturbation based identification method is proposed to obtain the FCAMs. Next, the method is implemented in a control-hardware-in-the-loop (CHIL) platform based on RTDS. Then with extensive CHIL tests, the FCAMs of both types of WTGs are obtained, and the impacts of frequency-coupling effects on SSO are validated. Finally, the characteristics of frequency-coupling effects and the root causes are further examined. This study is of important reference value to select appropriate models for oscillatory stability analysis.
What problem does this paper attempt to address?