Data-Driven System-Side Harmonic Impedance Estimation Method for UHVDC Converter Station

Haiwei Xie,Wentao Lv,Shengyuan Liu,Feng Chen,Zhenzhi Lin,Diya Zhou
DOI: https://doi.org/10.1109/isgt-asia.2019.8881665
2019-01-01
Abstract:With the increasing attention to power quality, the AC system-side harmonic impedance of the UHVDC converter station is of great significance for harmonic analysis, harmonic control and engineering construction. In this paper, a data-driven method based on the extracted typical data is proposed to estimate the system-side harmonic impedance. According to the equivalent harmonic analysis circuit of the UHVDC converter station, the 500kV AC bus of the UHVDC converter station is used as the Point of Common Coupling (PCC), and a measurement matrix is formed by taking the harmonic voltage and current of AC bus as observation data. Then, the Density-Based Spatial Clustering of Applications with Noise (DBSCAN) algorithm is applied to extract the typical data of different operating conditions of the converter station from the large measurement matrix. Finally, the validity and practicability of the method are verified by the PSCAD simulation model.
What problem does this paper attempt to address?