Improved Time Domain Piecewise Calculating Method for AC Side Harmonic Current of HVDC Systems

XUE Yinglin,XU Zheng,HUANG Ying,LI Xiaolin
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2010.31.014
2010-01-01
Abstract:Harmonic current calculation is the critical part in the design and configuration of AC filters in HVDC projects. A modified time domain piecewise algorithm was proposed,which can calculate both non-characteristic and characteristic harmonic currents in the AC side simultaneously. At first,based on the characteristics of HVDC systems,the harmonic voltages on the entrance of the DC line were assumed to be zero. This assumption decouples the harmonic current calculation process of the rectifier side and the inverter side,and avoids the modeling of the DC line in the harmonic current calculation. Secondly,the overlap angles were calculated accurately by considering the usual non-ideal factors,including the negative sequence fundamental voltage and the background harmonic voltages on the AC side,the unsymmetrical firing angles and the imbalance of converting transformer impedances. This ensures an exact partition of the commutation interval and the non-commutation interval,which has an important influence on the non-characteristic harmonic computation. The effect of the DC current ripple was also taken into account in the calculation of the AC side harmonic current. The validity of the proposed method was demonstrated by comparison with the simulation results of PSCAD/EMTDC. It shows the proposed method is fast and accurate,and can meet the requirement of HVDC filter design for practical projects.
What problem does this paper attempt to address?