Experimental study on vertical rigid and flexible polyurethane fire suppression using water spray

Hengze Zhao,Ye Li,Yipei Qi,Xuanmeng Dong,Yongming Zhang,Qixing Zhang
DOI: https://doi.org/10.1177/0892705719879185
IF: 3.0272
2022-01-01
Journal of Thermoplastic Composite Materials
Abstract:A series of vertical fire suppression experiments on rigid polyurethane (RPU) and flexible polyurethane (FPU) with/without water spray were conducted in a standard chamber. A new video processing method was developed to determine the pyrolysis front position of wind-aided flame. Averaged flame height, carbon monoxide/hydrogen cyanide concentration, view factors, and extinguishing time were determined with operating pressure varying from 0.15 MPa to 0.4 MPa. The experimental study showed that water spray would suppress RPU/FPU fire mainly by fuel surface cooling. Furthermore, the perfect water spray pressure for RPU/FPU fire suppression was 0.3 MPa and the corresponding water application rate was 0.7511 mg/(cm(2)center dot s).
What problem does this paper attempt to address?