General Principle of Asynchronous Segment for AC/DC Synchronous Power Systems
Huanfeng DONG,Zheng XU,Yingchun QIAN,Dajun SI,Pengcheng SONG,Facai XING
DOI: https://doi.org/10.13336/j.1003-6520.hve.20170628010
2017-01-01
Abstract:With the successive commission of long-distance large-capacity DC transmission systems,the regional grid interconnections present new AC/DC hybrid interconnection characteristics of high voltage,long distance,wide area,and large capacity power exchange.First,we present three basic structures of DC links in regional power grid interconnections,and the outage of large capacity DC links is liable to cause angle instability of the two side AC systems.Then,we propose AC transmission corridor strength index,AC/DC transmission corridor strength ratio index,and AC transmission corridor efficiency index from the aspects of power system security and transmission economy efficiency,which is able to represent the AC transmission capacity,strong DC weak AC degree,and AC corridor efficiency quantitatively.Finally,the indexes are utilized in the four-province grid synchronously interconnected case of South China Grid in 2030.It is indicated that the Yunnan sending corridor is a typical strong-DC weak-AC transmission corridor,and the transient stability margin and AC transmission corridor efficiency index are low.It is recommended to unite the AC corridors,and the N-1 and N-2 transient simulation results also verify the above calculated results.